Quantcast
 
 
  Search
 
 
 
PVI-5000* & PVI-6000*
 
AE Solar Products
 

The revolutionary switching technology utilized in the Aurora inverter includes CoolMOS™and Insulated Gate Bi-polar Transistors (IGBT’s) to reduce switching losses.

Aurora has been designed with large de-rating criteria on all critical components, achieving an extremely robust and reliable inverter designed to last for 25 years and to deliver true maximum output
power on a continuous basis. With this design concept we achieve peak efficiencies of over 97% .

*Magnetek is a distributor of the Aurora PVI-5000 & PVI-6000.


PVI-5000_6000

Brochure | Manual(6000) | Aurora Software Designer*

*Note - Enable Macros before using.

 

Benefits

  • Dual input section to process two strings with independent MPPT (6000W max models)
  • IP65 (NEMA 4) ruggedized, completely sealed unit to stand the harshest environmental conditions
  • High speed MPPT for real time power tracking and improved energy harvesting
  • Compact size and high power density: 6000W (6000W max) of output power
    in a box just 981,5mm x 325mm x 195mm
  • Front heatsink keeps the unit cleaner and more efficient over time
  • Transformerless operation for highest efficiency: up to 97% (96,5% C.E.C)
  • DC disconnect switch (2 x 25A/600Vdc) meet
  • NEC Standard, Article 690 “Solar Photovoltaic System”
  • Reverse polarity protection minimizes chance of damage due to mis-wiring
  • High overload capability: works up to 6000W under most ambient conditions
  • True Sine Wave Output
  • Anti-islanding Protection
  • Certified grid connected operation according to UL1741 & CSA-C22.2 N.107.1-01
  • LCD Display on the front to monitor the main parameters
  • Integrated RS-485 serial communication
 

  Characteristics

PVI-5000-OUTD PVI-6000-OUTD

  Power Rating Ac (W)

5000
6000

  Absolute Max Voltage (Vdc)

600
600

  Max. Power Tracking Window range (Vdc)

90 to 580 (360 nominal)
90 to 580 (360 nominal)

  Array Configuration
  (Mac. Idc=18 A for each channel)

One or two arrays with common negative and independent MPPT
One or two arrays with common negative and independent MPPT

  Nominal AC Voltage (Range) (Vms)

Single phase 208; 240; 277 (setting required)
Single phase 208; 240; 277 (setting required)

  Nominal AC Frequency (Hz)

60
60
  Line Power Factor 1
1

  Maximum AC Line Current (Arms)

30
30

  AC Current Distortion (%)

<2% THD at rated power
with finewave voltage
<2% THD at rated power
with finewave voltage

  Max Efficiency (%)

97 (96,5% C.E.C)
97 (96,5% C.E.C)

  Tare Losses (mW)

<300mW

<300mW

  Operating Ambient Temperature (°C)

-25 to +60
-25 to +60

  Enclosure Environmental Rating

NEMA 4X
NEMA 4X

  Relative Humidity

0-100% condensing
0-100% condensing

  Elevation

derated above 2.000 m (6,600ft)
derated above 2.000 m (6,600ft)

  Audible Noise (dBA)

<50@ 1m
<50@ 1m

  Size (height x width depth) (mm)

981,5mm x 325mm x 195mm
981,5mm x 325mm x 195mm

  Weight (kg)

30
30
 
 
  TERMS & CONDITIONS PRIVACY STATEMENT SALES & WARRANTY TERMS
© 2008 MAGNETEK, INC.

Overview | Solar Products | Wind Products | Fuel Cell Products | Manuals | Brochures