Characteristics |
PVI-CENTRAL-100 w/transformer |
PVI-CENTRAL-100-TL
w/o transformer |
Input Parameters |
|
Maximum recommended PV power (kWp), Total (master slave mode) Per Channel (multi-master mode) |
115.00
57.5 |
115.00
57.50 |
Absolute maximum input voltage (Vdc) |
600 |
600 |
MPPT input voltage range Vdc |
300-600 (400 nominal) |
300-600(400 nominal) |
Maximum input current (Adc), Master-slave mode Multi-master mode (per module)
|
320.00
160.00 |
320.00
160.00 |
Input Reflected Ripple voltage |
< 3% |
< 3% |
Number of DC inputs available
(multi-masterconfiguration)
|
2 |
2 |
Input overvoltage protections |
2 ( 1 of each input) |
2 ( 1 of each input) |
Output Parameters |
|
Nominal AC Output Power (kW) |
104.00 |
104.00 |
Nominal AC Output Current (Arms)
208 Vac version
480 Vac version |
280.00
120.00
|
280.00
N/A |
AC Output Voltage range (Vrms) |
3 x 200 +/-10% or 3x480 +/-10% |
3 x 200 +/-10% |
Nominal AC Frequency (Hz) |
50 / 60 |
50 / 60 |
Power Factor |
1 (@ Pac nominal) |
1 (@ Pac nominal) |
AC Current Harmonics (THD%) |
< 3% (@ Pac nominal) |
< 3% (@ Pac nominal) |
Inverter Switching Frequency (kHz) |
18 |
18 |
AC side overvoltage protection |
Yes |
Yes |
Conversion Efficiency |
|
Peak Efficiency % (@ Vin nom) |
96.3% |
97.42% |
CEC Efficiency % (@ Vin nom) 208 |
95% |
95% |
CEC Efficiency % (@ Vin nom) 480 |
95% |
N/A |
Environmental Parameters |
|
Environmental Protection Degree |
NEMA 2/NEMA 3R |
NEMA 2/NEMA 3R |
Operating Temperature Range |
-10°C...+50°C |
-10°C...+50°C |
Relative Humidity (non-condending) |
< 95% |
< 95% |
General Data |
|
Auxlilary Voltages Consumption (W) |
<0.2% of PACnom |
<0.2% of PACnom |
Night time losses (W) |
<30W |
<30W |
Local Communication |
1x RS485 + 1x RS485 (dedicated to String combiner-Box) |
1x RS485 + 1x RS485 (dedicated to String combiner-Box) |
Remote Communication (optional) |
Aurora Easy Control (Dial-Up, ISDN, Ethernet, DSL, GSM) |
Aurora Easy Control (Dial-Up, ISDN, Ethernet, DSL, GSM) |
User Interface |
2-lines Display (on each inverter module) |
2-lines Display (on each inverter module) |
Mechanical Characteristics |
|
Dimensions (WxHxD) (mm) (*) Output Air conduit not included |
1250 x 1570(*) x 810/49.2”x61.8”x31.8” |
1250 x 1570(*) x 810/49.2”x61.8”x31.8” |
Overall Weight (kg) |
900/1980 |
480/1056 |
55kW module Weight (kg) |
65/143 |
65/143 |
Required Ambient Air Cooling Flow |
2000m3/h/3600CFM |
2000m3/h/3600CFM |
Approvals |
|
EMC |
FCC part 15 |
FCC part 15 |
CE Compliance |
Yes |
Yes |
Grid connection (pending) |
DK5940 Ed. 2.2, VDEW, UL1741, RD1663/2000 |